FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
5 Components Replacement
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
140
Figure 5-71
Pulling up the reset button
2.
Press the reset button on the pressure operated switch.
3.
Flip the key to
Enable Control
rightward. Reset the extinguishant control panel by
pressing
Reset
on it. Then, reset the key to
Enable Control
leftward.
----End
Follow-up Procedure
Dispose of the removed warning signs indicator that is confirmed faulty.
5.5.4 Replacing a StroBell (CE)
Prerequisites
A spare StroBell of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: Phillips screwdriver, hex key, step ladder
Materials: spare StroBell
Documents: fire extinguishing device layout diagram (CE)
Skill requirement: fire engineer