FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
5 Components Replacement
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
169
Figure 5-94
Connecting battery cables
Distinguish the positive and negative battery terminals when connecting battery cables.
----End
Follow-up Procedure
Dispose of the removed extinguishant control panel batteries that are confirmed faulty.
5.6.9 Replacing a Fire Cylinder (CE)
Prerequisites
A spare fire cylinder of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Preparations
Tools: pipe wrench, pallet truck, Phillips screwdriver, adjustable wrench, protective gloves
Materials: spare fire cylinder, sealing tape
Documents: fire extinguishing device layout diagram (CE)
Skill requirement: fire engineer