Figure 5-95
Removing the pneumatic switch hose
Step 6
Loosen the straps on the fire cylinder.
Step 7
Remove the faulty fire cylinder from the installation position.
Step 8
Move the new fire cylinder to the installation position, and tighten the straps.
Keep the pressure gauge panel outwards so that people can view the reading.
Step 9
Connect the hose to the pneumatic switch.
Wrap the threads with sealing tape to ensure air tightness.
Step 10
Connect the fire cylinder to the fire extinguishing pipeline.
Wrap the threads with sealing tape to ensure air tightness.
1.
Connect the threaded adapter to the fire cylinder.