FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
5 Components Replacement
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
121
For the diagrams, see the initial configuration parameter manual for the solution in use.
Before replacing the fire cylinder, inform the related administrative departments of the
temporary downtime of the fire extinguishing system. After the replacement, inform the
administration department that the system has become operational.
Procedure
Step 1
Switch off the active and standby power supplies to the fire alarm control panel.
Figure 5-46
Switching off the active and standby power supplies
Step 2
Disconnect the interconnection cables between the electromagnetic valve and the fire alarm
control panel, as shown in
. Disconnect cables from the electromagnetic valve, as
shown in