FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
5 Components Replacement
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
172
2.
Connect the I-shaped connection pipe to the threaded adapter.
3.
Connect the high-pressure hose.
Step 11
Reinstall the electrical actuator to the container valve of the fire cylinder.
1.
Verify that the electrical actuator ejector is reset. If the ejector is not reset, press down
the ejector.
That the ejector is not reset may lead to extinguishant release.
The electrical actuator ejector is 11 mm long before being pressed down, and 7 mm long
after being pressed down.
Figure 5-96
Operating the electrical actuator ejector
2.
Align the electrical actuator and the container valve, and tighten the actuator clockwise.
Step 12
Switch on the input circuit breaker of the extinguishant control panel and connect the battery
cables to power on the panel.
----End
Follow-up Procedure
Dispose of the removed fire cylinder that is confirmed faulty.
5.6.10 Replacing the Extinguishant Control Panel (CE)
Prerequisites
A spare extinguishant control panel of the same model is available and functional.