![Huawei FusionModule 1000A40 Maintenance Manual Download Page 25](http://html.mh-extra.com/html/huawei/fusionmodule-1000a40/fusionmodule-1000a40_maintenance-manual_168404025.webp)
FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
3 Maintenance
Issue 04 (2018-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
17
Device
Operation
Check Standard
Maintenance Guide
fire extinguishing
pipeline, and
nozzle.
All devices of the
fire extinguisher are
free from rust on the
exterior, and the
coating is intact.
Repaint.
The lead seal and
safety signs on
hand-operated
devices of the fire
cylinder are intact.
Replace the electrical
actuator.
Check the pressure
pointer of the fire
cylinder.
The pressure pointer
is in the green zone.
Ask a fire engineer to check
whether the fire cylinder leaks
extinguishant. If leakage
occurs, the fire engineer
charges the extinguishant in
the local charging station.
Emergency
light
Disconnect the
power plug of the
emergency light.
The emergency light
turns on.
Replace the emergency light.
Smoke
detector
Check the smoke
detector indicator.
The indicator blinks
once every 6s.
Replace the smoke detector.
Heat
detector
Check the heat
detector indicator.
The indicator blinks
once every 6s.
Replace the heat detector.
3.2.7 Other Systems
Table 3-8
Monthly maintenance checklist for other systems
Maintena
nce Item
Operation
Standards
Compliance
Troubleshooting
Pre-fab.
module
paint
Check the
appearance of the
pre-fab. module.
The pre-fab.
module and
bases are free
from paint
flake-off, rust,
or corrosion.
If any part of the pre-fab. module is
damaged or corroded, maintain or
replace the damaged and corroded
part.
Pre-fab.
module
external
environmen
t
Check the pre-fab.
module external
environment.
No hazard or
potential
hazard exists
around the
pre-fab.
module.
If there is potential hazard or
pollutant around the pre-fab.
module, take workaround measures.