5.4.7 Replacing Batteries for the Fire Alarm Control Panel
(Standard)
Prerequisites
Spare fire alarm control panel batteries of the same model are available and functional.
Impact on the System
None
Preparations
Tools: protective gloves, step ladder, Phillips screwdriver
Materials: spare fire alarm control panel batteries
Documents: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer
For the diagrams, see the initial configuration parameter manual for the solution in use.
Procedure
Step 1
Switch off the standby power supply to the fire alarm control panel.
Figure 5-42
Positions of the active and standby power switches
Step 2
Use a Phillips screwdriver to remove the battery fixing plate.
Do not short-circuit the positive and negative terminals during the operation.