Diagnostics
109
3
Is fault isolation being performed at the director?
YES
NO
↓
Fault isolation is being performed at the HAFM appliance or
Embedded Web Server interface. Go to
4
Inspect both fan modules at the rear of the director. Fan module LEDs can be
inspected through the hexagonal cooling vents of the radio frequency interference
(RFI) shield.
Does inspection of a director fan module indicate a failure? Indicators include:
■
The amber LED is illuminated but not blinking (beaconing) on one or both
fan modules.
■
One or more cooling fans are not rotating.
YES
NO
↓
.
5
One or more cooling fans failed, and one or both fan modules must be removed
and replaced (“
■
If one or more fans in a module are operating, do not remove the fan module
unless the replacement is immediately available.
■
If a multiple fan failure caused a thermal shutdown, power on the director
after the fan modules are replaced (“
Note:
Do not remove a fan module unless the replacement module is available.
Operation of the director with only one fan module for an extended period may cause
one or more thermal sensors to post event codes.
Are the fan modules functioning?
NO
YES
↓
The director is operational. Exit MAP.
Contact the next level of support. Exit MAP.
Summary of Contents for StorageWorks 2/140 - Director Switch
Page 18: ...About this Guide 18 Director 2 140 Service Manual ...
Page 160: ...Diagnostics 160 Director 2 140 Service Manual ...
Page 262: ...FRU Removal and Replacement 262 Director 2 140 Service Manual ...
Page 270: ...Illustrated Parts Breakdown 270 Director 2 140 Service Manual ...
Page 318: ...Information and Error Messages 318 Error Messages ...
Page 388: ...Event Code Tables 388 Director 2 140 Service Manual ...