MX8000 Installation and Operation Guide
7–2
Table 7–1: Error Messages (cont’d)
LC
Error
Sys
Error
VFD Messages
Printer Message
Description
What to Do
✔
Expander
Trouble
Expander Trouble
Trouble with a device connected to the
SBUS.
✔
Expander Trbl
Rst
Expander Trouble
Restore
The trouble condition of a SBUS device was
corrected.
✔
AC Trouble
AC Trouble
AC power failure.
Check AC outlet and
AC power cord.
✔
AC Trouble Rst AC Trouble Restore AC power was restored.
Restores at 12VDC
after a low battery
condition.
✔
Battery Low
Restore
Battery Low
Restore
The backup battery power supply trouble
has been corrected.
✔
Battery Low
Battery Low
The backup battery is checked continually
every second. This message would be
displayed if the backup battery were set to
“Battery Bkp”. See Section 5.4.4. Indicates a
low battery when the voltage drops to 10.2
VDC or lower.
Check battery cables.
If they are OK
replace backup
battery.
✔
Local Program
Begin
Local Program
Begin User #
This message indicates the time a system
“installer” entered program mode.
✔
Local Program
End
Local Program End
User #
This message indicates the time a system
“installer” exited program mode.
✔
Local Program
Fail
Local Program Fail
User #
The receiver will stay in program mode for
15 minutes without any activity, then it will
time out and go back to normal mode. This
message indicates that an installer entered
programming and did not exit programming
before it timed out.
✔
Listen-in End
Listen-in End
A listen-in session completed
✔
Listen-in Begin
Listen-in Begin
A listen-in session started.
✔
System Date
Changed
System Date
Changed User #
An installer changed the system date.
✔
System Time
Changed
System Time
Changed User #
An installer changed the system time.
✔
Msg Queue Full
Message Queue
Full
Messages can be sent to automation
computer, a printer or can be manually
acknowledged. If one or more of these
devices does not respond to messages
being sent or manually acknowledged, the
message queue will fill up. When the
message queue is full the receiver will no
longer accept incoming calls.
Verify that messages
are acknowledged to
any printers,
automation software,
and while in manual
mode.
✔
Msg Queue Full
restore
Message Queue
Full restore
Indicates that the message queue full error
has been corrected.
✔
Main Computer
Trbl
Main Computer
Trouble
A communication problem exists between
the automation software and the receiver.
Check cable
connections. Verify
that the port is
configured properly.
✔
Main Computer
Rst
Main Computer
Restore
The communication error between the
receiver and the automation software has
been corrected.