MX8000 Installation and Operation Guide
5–28
To assign virtual receiver and virtual line numbers:
Notes:
•
If virtual receiver/line numbers are being used, DO NOT assign a hunt group number to a line. If a hunt
group number is assigned, it takes precedence and the virtual number will not be used.
•
Virtual receiver/line numbers will not be used when reporting an expander trouble. For an expander
troubles, the actual receiver/line number will be used.
1. Enter program mode. (See Section 5.1.)
2. Press
1
for general options.
3. Press
7
for virtual receiver/line numbers.
The display will flash on the virtual receiver number of the first line in the receiver:
L01=Rec#
00
Note:
The display will list all physical lines in the receiver.
4. Enter the desired virtual receiver number (a number from 00 to 99).
Notes:
•
If the virtual receiver number is programmed as zero for a given line then the system receiver number
will be used for the line’s receiver number and the line number will be the lines physical number.
•
If you are outputting to an automation computer using 685, CAPS, or CP-220 automation protocol, see
Table 5–10 on page 5–23 for valid entries for ID numbers 1–9 and A–Z.
5. Press
to advance to the virtual line number field.
6. Enter the desired virtual line number (a number from 001 to 099).
Note:
For proper reporting to an automation computer, use 008 or less when using 685 or CAPS
automation protocol or 015 or less if using CP-220 automation protocol.
7. Press
ENTER
MENU
to accept the entry and advance to the next line or press
if the line contains an error
that you need to correct.
8. Repeat steps 4 through 7 for each virtual receiver/line to be defined.
To Exit:
Press
until you return to the main menu.
5.5 Line Device Menu
Through the Line Device menu you can add a new Line Card
and edit, clear, or view existing Line Devices.
Table 5–11 lists the menu options available under Line
Device menu.
<Program Menu>
2=Line Device Menu
3 User List
< Exit
2
<Select Device Type>
1=MX8000-LC3
2 MX8000-LRR
3 MX8000-LC1
<Device Program>
1=Add Device
2 Edit Line
3 Copy Device(s)
¯
<Device Program>
4=Clear Device
5 View Device
< Exit Menu
¯
Figure 5–12: Choosing Line Device Menu
and Line Device Program Menu Items