MX8000 Installation and Operation Guide
5–14
Table 5–5: Communications Options and Description (cont’d)
Communications
Menu
Choices Options
Default
Comments
Ack Timeout
1-120 seconds
4 sec
15 seconds or less in UL applications. See Section
5.4.3.5 for programming steps.
<Cfg>
Term=013
Head=010
Ack=006
Nack=021
Time
Req=005
Time
Head=084
Time
Term=020
Only visible if ADEMCO 685, FBII220 or CAPS ONLY
format is selected.
Note: Setting Ack and Nack to 0 disables Ack and
Nack.
Y = Enabled
Sep
N = Disabled
✔
Only visible if SK9000 format is selected. When
enabled, a hex 05 is output for an account separator.
When not selected, a hex 2E is output for an account
separator.
Log
Records
✔
Y = Enabled
Enable
External
ID
N = Disabled
✔
Super
Char
s
No Data
Char
0
6.1
✔
Automation Cfg
(continued)
<ITI>
Generic
Revision 6.2
Only visible if ITI Gen or ITIComp format is selected.
Yes
✔
Printer
No
Yes
✔
Bkp Printer
No
Yes
✔
Auto Comp
No
Yes
✔
Bkp Auto Comp
No
Yes = will annunciate on the receiver sounder if an
event, trouble or fault condition occurs.
No = no annunciation if an event, trouble or fault
condition occurs.
See Section 5.4.3.6 for programming steps.
Yes
✔
Battery
No
Yes
✔
Device
No
Device corresponds to loss of communication with slave
or line card.
Yes
✔
Line Fault
No
Yes
✔
AC Power
No
Yes
✔
Buffer Full
No
Yes
✔
Listen In
No
Listen in must be set to No for UL installations.
Yes
✔
Annunciator Cfg
Call Pending
No