Section 5 – Programming
5–67
5.5.4.6 Ademco Auto Opt.
This selection is used to select the BFSK Auto output of Hi
Speed or 4/2, the 3/1 Restore output of Hi Speed or 3/1, the
4/2 Out Automation Conversion of codes 9, B, C, D, E, and
F of Hi Speed or Normal, combining 3/1 and 4/1 expanded
messages (Pulse Extended), Extended Output format, and
the FBII output of FBII Super Fast or FBII LAR300.
How to Set BFSK Auto Output
1. Follow the procedures in Section 5.5.4.
2. Press
6
for Ademco Auto Opt. menu (see Figure 5–
29).
The display Flashes on the
BFSK=
field.
6 Ademco Auto Opt.
< Exit Menu
BFSK=H/S 3/1Rstr=3/1
42Out=H/S FBI=S/Fast
<BFSK AutoOut<=Exit>
6
<Edit Line :01>
Pls=Ext ExtOut=H/S
Figure 5–29: MX8000–LC1 ADEMCO Auto
Output Options
3. Press
the
or
button to change the option from HiSpeed to 4/2 or vice versa.
4. When the desired setting is flashing press
ENTER
MENU
.
How to Set 3/1 Restore Output
1. Follow the procedures in Section 5.5.4.
2. Press
6
for Ademco Auto Opt. menu (see Figure 5–29).
3. Press
the
button.
The display Flashes on the
3/1 Rstr=
field.
4. Press
the
or
button to change the option from HiSpeed to 3/1 or vice versa.
5. When the desired setting is flashing press
ENTER
MENU
.
How to Set 4/2 Out
1. Follow the procedures in Section 5.5.4.
2. Press
6
for Ademco Auto Opt. menu (see Figure 5–29).
3. Press
.
The display Flashes on the
42Out=
field.
4. Press
the
or
button to change the option from HiSpeed to Normal or vice versa.
5. When the desired setting is flashing press
ENTER
MENU
.
6. To
exit
press
.
How to Set FBII Out
1. Follow the procedures in Section 5.5.4.
2. Press
6
for Ademco Auto Opt. menu (see Figure 5–29).
3. Press
.
The display Flashes on the
FBI=
field.