Section 5 – Programming
5–49
11. Press
to advance to the Min Ring Off (Min) field.
12. Enter a value from 100 to 800 ms for the Minimum Ring Off Time.
13. Press
to advance to the Ringer Off Error (RErr) field.
14. Enter a value from 0800 to 4400 ms for the Ringer Off Error Time.
15. Press
to advance to the Min # of Ring Periods (Min#) field.
16. Enter a value from 01 to 20 periods for the Minimum Number of Ringer Periods.
17. To exit press
.
To Change the Call Hang-Up Time:
Notes:
•
If the Event Release setting (see page 5–26) is "greater" than the Call Hang-Up setting, the receiver will
not disconnect the line (panel) until the Event Release time has expired.
•
The actual amount of time before the receiver disconnects a line may at times be greater than the
actual programmed value for Call Hang-Up Time. An event in progress (Event Release) has to
complete before the call hang-up takes affect.
1. Follow the procedures in Section 5.5.2.
2. Press
5
for Miscellaneous Line Options menu.
3. Press
until the display flashes on the
HngUp
field.
4. Enter the desired value from the keypad or press the
or
button to change the number of
seconds.
5. When the desired number of seconds is flashing press
ENTER
MENU
.
6. To
exit
press
.
5.5.2.6 Ademco Auto Opt.
This selection is used to select the BFSK Auto output of Hi
Speed or 4/2, the 3/1 Restore output of Hi Speed or 3/1, the
4/2 Out Automation Conversion of codes 9, B, C, D, E, and
F of Hi Speed or Normal, combining 3/1 and 4/1 expanded
messages (Pulse Extended), Extended Output format, and
the FBII output of FBII Super Fast or FBII LAR300.
How to Set BFSK Auto Output
1. Follow the procedures in Section 5.5.2.
2. Press
6
for Ademco Auto Opt. menu (see Figure 5–
20).
The display Flashes on the
BFSK=
field.
6 Ademco Auto Opt.
7 Line Gain Opt.
BFSK=H/S 3/1Rstr=3/1
42Out=H/S FBI=S/Fast
<BFSK AutoOut<=Exit>
6
<Edit Line :01>
Pls=Ext ExtOut=H/S
< Exit Menu
Figure 5–20: MX8000–LC3 ADEMCO Auto
Output Options