Section 5 – Programming
5–13
Table 5–5: Communications Options and Description (cont’d)
Communications
Menu
Choices Options
Default
Comments
38400
✔
19200
9600
7200
4800
2400
1200
600
300
Baud
110
7
D (# Data Bits)
8
✔
1
✔
S (# Stop Bits)
2
Even
Odd
P (Parity)
No
✔
Yes
✔
PortMon (Port
Monitor)
No
When set to Yes (recommended) the computer ready
line is monitored.
Hdwr
✔
Unidirectional communication
Sfwr
F (Flow)
None
No supervision
Com Port 1
Init Str
(Initialization
String)
Two 20-character ESC command sequences.
See Section 5.4.3.4 for step-by -step instructions.
Com Port 2
Same as Com Port 1
Par Port (Parallel
Port)
Edit Init Str
(Initialization
String)
Two 20-character ESC command sequences.
See Section 5.4.3.4 for step-by -step instructions.
SK9000
ADEM 8000
✔
ITI Gen
ITIComp
ADEM 685
FBII 220
Format
CAPS
See Section 5.4.3.5 for programming steps.
See Section 8 for more information on automation
formats.
Y = Enabled
Hex
N = Disabled
✔
When Hex Mode is enabled, any call data that is
determined to be bad data will be output in Hex format.
Only visible if ADEM 8000 or SK9000 format is
selected.
Y = Enabled
See Section 5.4.3.5 for programming steps.
Heartbeat
N = Disabled
✔
Automation Cfg
Time (of
Heartbeat)
10-600 seconds
45 sec
How often a supervisory signal (a heartbeat) is sent to
the automation computer. See Section 5.4.3.5 for
programming steps.