4
−
80
Inverter Ready Signal
The inverter outputs the inverter ready signal (IRDY) when it is ready for operation
(i.e. when it can receive an operational command).
Option
Code
Terminal
Symbol
Function Name
State
Description
50
IRDY
Inverter ready signal
ON
The inverter is ready to accept the operation
command
OFF
The inverter is not ready to accept the operation
command
Valid for inputs:
11, 12, AL0 – AL2
Example for terminal [11] (default output
configuration shown – see
page 3-90
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
page 4-52 and 3-90
):
See I/O specs on
page 4-6
Required settings
C038
,
C039
Notes:
- The inverter can recognize only the operation
command is given while the IRDY signal is given
out
- If the IRDY signal is not given out, check whether
the input power supply voltage (connect to the R,
S, and T terminals) is within the range of
specification
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
IRDY
RY
Inverter output
terminal circuit
CM2
11
IRDY