Recommended ferrule
For safe wiring and reliability, it is recommended to use following ferrules.
Wire size
mm
2
(AWG)
Model name of
ferrule *
L [mm]
Φ
d [mm]
Φ
D [mm]
0.25 (24)
AI 0.25-8YE
12.5
0.8
2.0
0.34 (22)
AI 0.34-8TQ
12.5
0.8
2.0
0.5 (20)
AI 0.5-8WH
14
1.1
2.5
0.75 (18)
AI 0.75-8GY
14
1.3
2.8
* Supplier: Phoenix contact
Crimping pliers: CRIPMFOX UD 6-4 or CRIMPFOX ZA 3
How to connect?
(1) Push down an orange actuating lever by a slotted screwdriver (width 2.5mm max.).
(2) Plug in the conductor.
(3) Pull out the screwdriver then the conductor is fixed.
8
L
Φ
d
Φ
D
Push down an
orange actuating
lever.
2.5mm
Plug in the
conductor.
Pull out the
screwdriver to fix
the conductor.