3
−
21
Jog Frequency –
The jog speed setting is used whenever the Jog command is active.
The jog speed setting range is arbitrarily limited to 10 Hz, to provide safety during
manual operation. The acceleration to the jog frequency is instantaneous, but you can
choose from three modes for the best method for stopping the jog operation.
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Lnitial data
Units
A038
Jog frequency
Defines limited speed for jog,
range is from start frequency to
9.99 Hz
Define how end of jog stops the
motor; six options:
00
…
Free-run stop (invalid
during run)
01
…
Controlled deceleration
(invalid during run)
02
…
DC braking to stop(invalid
during run)
03
…
Free-run stop (valid during
run)
04
…
Controlled deceleration
(valid during run)
05
…
DC braking to stop(valid
during run)
6.00 Hz
A039
Jog stop mode
U
04
−
Note 1: For jogging operation, turn JG terminal ON at first and then turn FW or RV terminal
on.
Note 2: When jogging stop mode A039=02 or 05, DC braking data is needed.
Note 3: During jogging operation, frequency can be set with output frequency setting F001.
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...