PID Loop Configuration
The inverter’s PID loop algorithm is configurable for various applications.
PID Output Limit -
The PID loop controller has a built-in output limit function. This
function monitors the difference between the PID setpoint and the loop output (inverter
output frequency), measured as a percentage of the full scale range of each. The limit is
specified by parameter
A078
.
•
When the difference |(Setpoint – loop output)| is smaller than or equal to the
A078
limit value, the loop controller operates in its normal linear range.
•
When the difference |(Setpoint – loop output)| is larger than the
A078
limit value,
the loop controller changes the output frequency as needed so that the difference
does not exceed the limit.
The diagram below shows PID setpoint changes and the related output frequency
behavior when a limit value in
A078
exists.
Deviation (error) Inversion -
In typical heating loops or ventilation loops, an increase in
energy into the process results in an
increasing
PV. In this case, the Loop Error = (SP –
PV). For cooling loops, an increase in energy into the process results in a
decreasing
PV.
In this case, the Loop Error = –(SP – PV). Use
A077
to configure the error term.
t
Output limit
PID Setpoint
Output limit
Limit imposed
on output
Limit imposed
on output
A078
A078
%
Output freq.
Σ
PID
calculation
SP
+
Error
Freq.
PV
-
PV from process with
positive correlation
A077
=
00
Σ
PID
calculation
SP
-
Error
Freq.
PV
+
PV from process with
negative correlation
A077
=
01
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...