Message Configuration: Query
Slave address:
•
This is a number of 1 to 32 assigned to each inverter (slave). (Only the inverter
having the address given as a slave address in the query can receive the query.)
•
When slave address “0” is specified, the query can be addressed to all inverters
simultaneously. (Broadcasting)
•
In broadcasting, you cannot call and loop back data.
•
Slave Address 1-247 in Modbus specification. When master address the slave
250-254, broadcast toward specific slave address. Slave doesn’t answer back. And
this function is valid for the write command (05h, 06h, 0Fh, 10h)
Slave address
Broadcast to
250
(
FAh
)
Broadcast to Slave address 01to 09
251
(
FBh
)
Broadcast to Slave address 10 to 19
252
(
FCh
)
Broadcast to Slave address 20 to 29
253
(
FDh
)
Broadcast to Slave address 30 to 39
254
(
FEh
)
Broadcast to Slave address 40 to 247