4
−
66
External Brake Related Output Signals
These signals are used with brake control function.
To output the warning signals, assign function “
19
(BRK)” and “
20
(BER)” to the
intelligent output terminals [11] and [12], or to the relay output terminal.
Refer to chapter 3 for detailed explanation of the brake control function.
Option
Code
Terminal
Symbol
Function Name
State
Description
19
BRK
Brake release signal
ON
Brake is ready to be released
OFF
Brake is not ready to be released
20
BER
Brake error signal
ON
Brake error has occurred
OFF
Brake is working properly
Valid for inputs:
11, 12, AL0 – AL2
Example for terminal [11] (default output
configuration shown – see
page 3-90
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
page 4-52 and 3-90
):
See I/O specs on
page 4-6
Required settings
b120
~
b127
Notes:
•
The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative-going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
RY
Inverter output
terminal circuit
CM2
11
BRK/BER
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
BRK/BER
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...