Sensorless Vector Control
This sensorless vector control enables the inverter to accurately operate the motor with
a high starting torque, even at low speed. It estimates and controls the motor speed and
output torque based on the inverter output voltage, output current, and the set motor
constants on the inverter. To use this function, specify “
03
” for the V/F characteristic
curve selection (
A044
/
A2444
).
In prior to use this function, be sure to make optimum setting of the motor constants,
which is described before.
When using this function, observe the following precautions:
(1)
If you use the inverter to drive a motor of which the capacity is two class lower than
the maximum applicable capacity of the inverter, you may not be able to obtain
adequate motor characteristics.
(2)
If you cannot obtain the desired characteristics from the motor driven under the
SLV control, readjust the motor constants according to the symptom, as described in
the table below.
Status
Symptom
Adjustment method
Adjustment
item
Powering
Momentary speed variation is
negative
Increase the motor constant R2 step by step from
the set value up to 1.2 times of the set value
H021
/
H221
Momentary speed variation is
positive
Decrease the motor constant R2 step by step
from the set value up to 0.8 times of the set value
H021
/
H221
Regeneration
Torque is insufficient at low
speed (~ few Hz)
Increase the motor constant R1 step by step from
the set value up to 1.2 times of the set value
H020
/
H220
Increase the motor constant Io step by step from
the set value up to 1.2 times of the set value
H023
/
H223
Starting
Motor generates an impact at
start
Reduce the motor constant J from the set value
H024
/
H224
Decrease the speed response factor
H005
/
H205
Motor runs backward for short
moment at start
Set 01 (enable) on reverse run protection function
(b046)
b046
Decelerating
Motor runs unsteadily
Decrease the speed response factor
H005
/
H205
Decrease the motor constant J from the set value
H024
/
H224
Low frequency
operation
Motor rotation is unstable
Increase the motor constant J from the set value
H024
/
H224
Increase the speed response factor
H005
/
H205
Note 1) When driving a motor of which the capacity is one class lower than the inverter,
adjust the torque limit (
b041
to
b044
) so that the value “
α
” calculated by the
expression below does not exceed 200%. Otherwise, the motor may not be burnt.
α
= “torque limit” x (inverter capacity) / (motor capacity)
(Example) When the inverter capacity is 0.75kW and the motor capacity is 0.4kW,
the torque limit value is calculated as follows, based on the
assumption that the value
α
should be 200%:
Torque limit (
b041
to
b044
) =
α
x (motor capacity) / (inverter capacity)
= 2.0 x (0.4kW)/(0.75kW) = 106%
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...