Forward Rotation, Reverse Rotation Signals
Forward Rotation signal-
The inverter continues to output the forward rotation signal
(FWR) while it is driving the motor for forward operation. The FWR signal is turned off
while the inverter is driving the motor for reverse operation or stopping the motor.
Reverse Rotation signal -
The inverter continues to output the forward rotation signal
(RVR) while it is driving the motor for reverse operation. The RVR signal is turned off
while the inverter is driving the motor for forward operation or stopping the motor.
Option
Code
Terminal
Symbol
Function Name
State
Description
51
FWR Forward
rotation
ON
Inverter is driving the motor for forward operation
OFF
Inverter is driving the motor for reverse operation, or
the motor is stopped
52
RVR
Reverse rotation
ON
Inverter is driving the motor for reverse operation
OFF
Inverter is driving the motor for forward operation, or
the motor is stopped
Valid for inputs:
11, 12, AL0 – AL2
Example for terminal [11] (default output
configuration shown – see
page 3-90
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
page 4-52 and 3-90
):
See I/O specs on
page 4-6
Required settings
Notes:
Output freq.
Forward rotation signal (FWR)
Reverse rotation signal (RVR)
RY
Inverter output
terminal circuit
CM2
11
FWR
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
FWR
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...