3
−
86
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
20
STA Start
(3-wire interface)
ON
Starts the motor rotation
OFF No change to present motor status
21
STP Stop
(3-wire interface)
ON
Stops the motor rotation
OFF No change to present motor status
22
F/R FWD,
REV
(3-wire interface)
ON
Selects the direction of motor rotation: ON = FWD.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction
OFF Selects the direction of motor rotation: OFF = REV.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction
23
PID PID
Disable
ON
Temporarily
disables PID loop control. Inverter output
turns OFF as long as PID Enable is active (
A071
=
01
)
OFF Has no effect on PID loop operation, which operates
normally if PID Enable is active (
A071
=
01
)
24
PIDC
PID Reset
ON
Resets the PID loop controller. The main
consequence is that the integrator sum is forced to zero
OFF No effect on PID controller
27
UP
Remote Control UP
Function (motorized
speed pot.)
ON
Accelerates (increases output frequency) motor from
current frequency
OFF Output to motor operates normally
28
DWN
Remote Control Down
Function (motorized
speed pot.)
ON
Decelerates (decreases output frequency) motor
from current frequency
OFF Output to motor operates normally
29
UDC
Remote Control Data
Clearing
ON
Clears the UP/DWN frequency memory by forcing it
to equal the set frequency parameter F001. Setting
C101
must be set=
00
to enable this function to work
OFF UP/DWN frequency memory is not changed
31
OPE
Operator Control
ON
Forces the source of the output frequency setting
A001
and the source of the Run command
A002
to be
from the digital operator
OFF Source of output frequency set by
A001
and source
of Run command set by
A002
is used
32
SF1 Multi-speed
Select,
Bit operation Bit 1
ON
Bit encoded speed select, Bit 1, logical 1
OFF Bit encoded speed select, Bit 1, logical 0
33
SF2 Multi-speed
Select,
Bit operation Bit 2
ON
Bit encoded speed select, Bit 2, logical 1
OFF Bit encoded speed select, Bit 2, logical 0
34
SF3 Multi-speed
Select,
Bit operation Bit 3
ON
Bit encoded speed select, Bit 3, logical 1
OFF Bit encoded speed select, Bit 3, logical 0
35
SF4 Multi-speed
Select,
Bit operation Bit 4
ON
Bit encoded speed select, Bit 4, logical 1
OFF Bit encoded speed select, Bit 4, logical 0
36
SF5 Multi-speed
Select,
Bit operation Bit 5
ON
Bit encoded speed select, Bit 5, logical 1
OFF Bit encoded speed select, Bit 5, logical 0
37
SF6 Multi-speed
Select,
Bit operation Bit 6
ON
Bit encoded speed select, Bit 6, logical 1
OFF Bit encoded speed select, Bit 6, logical 0
38
SF7 Multi-speed
Select,
Bit operation Bit 7
ON
Bit encoded speed select, Bit 7, logical 1
OFF Bit encoded speed select, Bit 7, logical 0
39
OLR Overload
Restriction
Source Changeover
ON
Perform overload restriction
OFF Normal operation
40
TL
Torque Limit Selection
ON
Setting of
b040
is enabled
OFF Max. torque is limited with 200%
41
TRQ1
Torque limit switch 1
ON
Torque limit related parameters of Powering/regen,
and FW/RV modes are selected by the combinations
of these inputs.
OFF
42
TRQ2
Torque limit switch 2
ON
OFF
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...