B
−
22
Func.
code
Name
Data/Range
For
Description
C072
Modbus address
1 to 247
ALL Network address
C076
Selection of the operation after
communication error
00 ALL
tripping
01
ALL tripping
after
decelerating
and stopping the motor
02 ALL
ignoring
errors
03
ALL stopping the motor after
free-running
04
ALL decelerating and stopping
the motor
C077
Communication timeout limit
0.00 ALL
Disabled
0.01
~
99.99
ALL [sec.]
C078
Communication wait time
0.
~
1000.
ALL [ms]
C096 Communication
selection
00
-
Modbus-RTU
01 B
EzCOM
02 A
EzCOM
< Admin. inverter >
C098
EzCOM start adr. of master
01 to 08
A
C099
EzCOM end adr. of master
01 to 08
A
C100
EzCOM starting trigger
00
A
Input terminal (Note 2)
01 A
Always
P140
EzCOM the number of data
1 to 5
M
P141
EzCOM destination 1 adderss
1 to 247
M
(Note 3)
P142
EzCOM destination 1 register
0000 to FFFF
M
P143
EzCOM source 1 register
0000 to FFFF
M
P144
EzCOM destination 2 adderss
1 to 247
M
P145
EzCOM destination 2 register
0000 to FFFF
M
P146
EzCOM source 2 register
0000 to FFFF
M
P147
EzCOM destination 3 adderss
1 to 247
M
P148
EzCOM destination 3 register
0000 to FFFF
M
P149
EzCOM source 3 register
0000 to FFFF
M
P150
EzCOM destination 4 adderss
1 to 247
M
P151
EzCOM destination 4 register
0000 to FFFF
M
P152
EzCOM source 4 register
0000 to FFFF
M
P153
EzCOM destination 5 adderss
1 to 247
M
P154
EzCOM destination 5 register
0000 to FFFF
M
P155
EzCOM source 5 register
0000 to FFFF
M
C001~
C007
Input terminal function
81
A
485: start EzCOM
Which parameters to be set?
ALL : Set all inverters in the network.
A : Set admin. inverter (address=1) only.
B : Set all inverters except admin. inverter.
M : Set master inverters configured in C098 to C099 of admin. inverter.
Note 5: Address of Administrative inverter is to be set 01 (C072=01).
Note 6: When selection of operation after communication error is set other than “ignoring errors
(C076=02)”, EzCOM function is interrupted in case of communication timeout on administrative inverter.
In this case, please power off/on or reset (on/off RES terminal) to recover.
Note 7:.If EzCOM starting trigger is set as input terminal (C100=00), be sure to configure 81 in one of
input terminals.
Note 8: If EzCOM starting trigger is set as always (C100=01), administrative inverter starts to send the
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...