3
−
80
Function
High frequency mode
Standard mode
Rating HD
HD
ND
Max. freq. (
A004
) 1000Hz 400Hz 400Hz
Start freq. (
b082
)
0.10 to 100.0 (Hz)
0.10 to 9.99 (Hz)
0.10 to 9.99 (Hz)
Carrier freq. (
b083
)
2.0 to 10.0 (kHz)
2.0 to 15.0 (kHz)
2.0 to 10.0 (kHz)
V/f characteristic curve
(
A044
)
00: Const. torque
01: Reduced torque
02: Free V/f
00: Const. torque
01: Reduced torque
02: Free V/f
03: SLV
00: Const. torque
01: Reduced torque
02: Free V/f
HD mode
b049
:
00
d060
:
1-C
ND mode
b049
:
01
d060
:
1-v
High freq. mode
d060
:
H-1
Normal mode
(~
400Hz
)
HD mode
High freq
(~
1000Hz
)
b171
=
01
+ init.
b049
=
01
b049
=
00
b171
=
02
+ init.
b171
=
02
+ init.
ND mode
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...