Running Time and Power On Time Over Signal
The inverter outputs the operation time expiration signal and power on time expiration
signal.
To enable this function, assign “
11
(RNT)”, and/or “
12
(ONT)” to intelligent output
terminals.
Option
Code
Terminal
Symbol
Function Name
State
Description
11
RNT
Run time expiration
signal
ON
Accumulated operation time of the inverter exceeds
the set value of
b034
OFF
Accumulated operation time of the inverter does not
exceed the set value of
b034
12
ONT
Power ON time
expiration signal
ON
Accumulated power on time of the inverter exceeds
the set value of
b034
OFF
Accumulated power on time of the inverter does not
exceed the set value of
b034
Valid for inputs:
11, 12, AL0 – AL2
Example for terminal [11] (default output
configuration shown – see
page 3-90
):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
page 4-52 and 3-90
):
See I/O specs on
page 4-6
Required settings
B034
Notes:
•
The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative-going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
RY
Inverter output
terminal circuit
CM2
11
RNT
AL1
Power
supply
Load
AL0
AL2
Inverter logic
circuit board
ONT
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...