3
−
96
Electronic Thermal Warning Output –
Please refer to page 3-39 for detailed information.
Zero speed detection Output –
The inverter outputs the 0Hz speed detection signal
when the inverter output frequency falls below the threshold frequency specified in the
zero speed detection level (
C063
).
To use this function, assign parameter “
21
” to one of the intelligent output terminals
[11] to [12] (
C021
to
C022
), or to the alarm relay output terminal (
C026
).
This function applies to the inverter output frequency when the V/F characteristic
curve selection is based on the constant torque (VC), reduced torque (VP), free-V/F,
sensorless vector control, or 0Hz range sensorless vector control.
Heat Sink Overheat Warning Output –
The inverter monitors the temperature of its
heat sink, and outputs the heat sink overheat warning (OHF) signal when the
temperature exceeds the heat sink overheat warning level specified in parameter
C064
.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Lnitial data
Units
C040
Output mode of overload
warning
Two option codes:
00
…
During accel., decel. and
constant speed
01
…
During constant speed only
U
01
C041
Overload warning level
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
U
Rated current
x 1.15
C241
Overload warning level,
2
nd
motor
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
U
Rated current
x 1.15
C042
Frequency arrival setting
for acceleration
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
U
0.0
C043
Frequency arrival setting
for deceleration
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
U
0.0
C044
PID deviation level
Sets the allowable PID loop error
magnitude (absolute value),
SP-PV, range is 0.0 to 100%
U
3.0
C045
Frequency arrival setting
2 for acceleration
Set range is 0.0 to 400.0 Hz
U
0.00
C046
Frequency arrival setting
2 for deceleration
Set range is 0.0 to 400.0 Hz
U
0.00
C052
PID FBV output
high limit
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0
to 100%
U
100.0 %
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...