xi
CAUTION: Do not stop operation by switching OFF electromagnetic contactors on the primary
or secondary side of the inverter.
When there has been a sudden power failure while an operation instruction is active, then the
unit may restart operation automatically after the power failure has ended. If there is a
possibility that such an occurrence may harm humans, then install an electromagnetic contactor
(Mgo) on the power supply side, so that the circuit does not allow automatic restarting after the
power supply recovers. If the optional remote operator is used and the retry function has been
selected, this will also cause automatic restarting when a Run command is active. So, please be
careful.
CAUTION: Do not insert leading power factor capacitors or surge absorbers between the output
terminals of the inverter and motor.
When there has been a sudden power failure while an operation instruction is active, then the
unit may restart operation automatically after the power failure has ended. If there is a
possibility that such an occurrence may harm humans, then install an electromagnetic contactor
(Mgo) on the power supply side, so that the circuit does not allow automatic restarting after the
power supply recovers. If the optional remote operator is used and the retry function has been
selected, this will also cause automatic restarting when a Run command is active. So, please be
careful.
Ground fault
interrupter
CAUTION: MOTOR TERMINAL SURGE VOLTAGE SUPPRESSION FILTER
(For the 400V CLASS)
In a system using an inverter with the voltage control PWM system, a voltage surge caused by
the cable constants such as the cable length (especially when the distance between the motor
and the inverter is 10m or more) and cabling method may occur at the motor terminals. A
dedicated filter of the 400V class for suppressing this voltage surge is available. Be sure to
install a filter in this situation.
Power
Input
Inverter
U, V, W
L1, L2, L3
Motor
PCS
FW
Power
Input
Ground fault
interrupter
L1, L2, L3
Inverter
U, V, W
Motor
Surge absorber
GND lug
Leading power
factor capacitor
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...