b038
Initial display selection
000
…
Func. code that SET key
pressed last displayed.(*)
001
~
030
…
d001
~
d030
displayed
201
…
F001
displayed
202
…
B display of LCD operator
U
001
−
B086
Frequency scaling
conversion factor
Specify a constant to scale the
displayed frequency for
D007
monitor, range is 0.01 to 99.99
U
1.00
−
b150
Display ex.operator
connected
When an external operator is
connected via RS-422 port, the
built-in display is locked and
shows only one "d" parameter
configured in:
d001
~
d030
U
001
−
b160
1st parameter of Dual
Monitor
Set any two "d" parameters in
b160 and b161, then they can be
monitored in d050. The two
parameters are switched by
up/down keys.
Set range:
d001
~
d030
U
001
−
b161
2nd parameter of Dual
Monitor
U
002
−
b163
Frequency set in monitoring Two option codes:
00
…
Freq. set disabled
01
…
Freq. set enabled
00
−
b164
Automatic return to the
initial display
10 min. after the last key
operation, display returns to the
initial parameter set by
b038
.
Two option codes:
00
…
Disable
01
…
Enable
00
−
b165
Ex. operator com. loss action Five option codes:
00
…
Trip
01
…
Trip after deceleration to a
stop
02
…
Ignore
03
…
Coasting (FRS)
04
…
Decelerates to a stop
02
−
(*) note: If the power is off with displaying “000” after the set, b038 comes when power is on
again.
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...