Automatic restart (retry) related parameters.
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Lnitial data Units
B001
Restart mode on power
failure / under-voltage trip
Select inverter restart method,
Five option codes:
00
…
Alarm output after trip, no
automatic restart
01
…
Restart at 0Hz
02
…
Resume operation after
frequency matching
03
…
Resume previous freq.
after freq. matching, then
decelerate to stop and
display trip info
04
…
Resume operation after
active freq. matching
U
00
−
B002
Allowable under-voltage
power failure time
The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the
restart mode is selected.
U
1.0 sec.
B003
Retry wait time before motor
restart
Time delay after under-voltage
condition goes away, before the
inverter runs motor again.
Range is 0.3 to 100 seconds.
U
1.0 sec.
B004
Instantaneous power failure
/ under-voltage trip alarm
enable
Three option codes:
00
…
Disable
01
…
Enable
02
…
Disable during stop and
decelerates to a stop
U
00
−
B005
Number of restarts on power
failure / under-voltage trip
events
Two option codes:
00
…
Restart 16 times
01
…
Always restart
U
00
−
b007
Restart frequency threshold
Restart the motor from 0Hz if
the frequency becomes less
than this set value during the
motor is coasting, range is 0 to
400Hz
U
0.00 Hz
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...