4
−
90
Analog Output Operation
In inverter applications it is useful to monitor the
inverter operation from a remote location or from the
front panel of an inverter enclosure. In some cases,
this requires only a panel-mounted volt meter. In
other cases, a controller such as a PLC may provide
the inverter’s frequency command, and require
inverter feedback data (such as output frequency or
output current) to confirm actual operation. The
analog output terminal [AM] serves these purposes.
The inverter provides an analog voltage output on terminal [AM] with terminal [L] as
analog GND reference. The [AM] can output inverter frequency or current output value.
Note that the voltage range is 0 to +10V (positive-going only), regardless of forward or
reverse motor rotation. Use
C028
to configure terminal [AM] as indicated below.
Func.
Code
Description
C028
00
Inverter output frequency
01
Inverter output current
02
Inverter output torque
03
Digital output freqnency
04
Inverter output goltage
05
Inverter input power
06
Electronic Thermal Load
07
LAD frequency
08
Digital current monitor
10
Cooling fin temperature
12
General purpose
15
Pulse train
16
Option
AM H O OI L
+
-
A GND
Analog
Voltage
Output
10VDC
full scale,
2mA max
See I/O specs on page4-6
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...