3
−
85
Input Function Summary Table
–
This table shows all thirty-one intelligent input
functions at a glance. Detailed description of these functions, related parameters and
settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on
page 4-8.
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
00
FW FORWARD
Run/Stop
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
01
RV Reverse
Run/Stop
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
02
CF1 *1
Multi-speed Select,
Bit 0 (LSB)
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
03
CF2
Multi-speed Select,
Bit 1
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
04
CF3
Multi-speed Select,
Bit 2
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
05
CF4
Multi-speed Select,
Bit 3 (MSB)
ON
Binary encoded speed select, Bit 3, logical 1
OFF
Binary encoded speed select, Bit 3, logical 0
06
JG Jogging
ON
Inverter is in Run Mode, output to motor runs at jog
parameter frequency
OFF
Inverter is in Stop Mode
07
DB
External DC braking
ON
DC braking will be applied during deceleration
OFF
DC braking will not be applied
08
SET
Set (select) 2nd Motor
Data
ON
The inverter uses 2nd motor parameters for
generating frequency output to motor
OFF
The inverter uses 1st (main) motor parameters for
generating frequency output to motor
09
2CH
2-stage Acceleration
and Deceleration
ON
Frequency output uses 2nd-stage acceleration and
deceleration values
OFF
Frequency output uses standard acceleration and
deceleration values
11
FRS Free-run
Stop
ON
Causes output to turn OFF, allowing motor to free
run (coast) to stop
OFF
Output operates normally, so controlled
deceleration stop motor
12
EXT External
Trip
ON
When assigned input transitions OFF to ON,
inverter latches trip event and displays
E 12
OFF
No trip event for ON to OFF, any recorded trip
events remain in history until reset
13
USP
Unattended Start
Protection
ON
On powerup, the inverter will not resume a Run
command (mostly used in the US)
OFF
On powerup, the inverter will resume a Run
command that was active before power loss
14
CS
Commercial power
source switchover
ON
Motor can be driven by commercial power
OFF
Motor is driven via the inverter
15
SFT Software
Lock
ON
The keypad and remote programming devices are
prevented from changing parameters
OFF
The parameters may be edited and stored
16
AT
Analog Input
Voltage/Current Select
ON
Refer to “Analog Input Settings” on page 3-13.
OFF
18
RS Reset
Inverter
ON
The trip condition is reset, the motor output is
turned OFF, and powerup reset is asserted
OFF
Normal power-ON operation
19
PTC
PTC thermistor Thermal
Protection
(C005 only)
ANLG
When a thermistor is connected to terminal [5] and
[L], the inverter checks for over-temperature and
will cause trip event and turn OFF output to motor
OPEN
A disconnect of the thermistor causes a trip event,
and the inverter turns OFF the motor
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...