It is possible for the inverter to retain the frequency set from the [UP] and [DWN]
terminals through a power loss. Parameter
C101
enables/disables the memory. If
disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use
the [UDC] terminal to clear the memory and return to the original set output
frequency.
Option
Code
Terminal
Symbol
Function Name
State
Description
27
UP
Remote Control UP
Function (motorized
speed pot.)
ON
Accelerates (increases output frequency) motor
from current frequency
OFF
Output to motor operates normally
28
DWN Remote
Control
DOWN Function
(motorized speed
pot.)
ON
Decelerates (increases output frequency) motor
from current frequency
OFF
Output to motor operates normally
29
UDC
Remote Control Data
Clear
ON
Clears the Up/Down frequency memory
OFF
No effect on Up/Down memory
Valid for inputs:
C001
~
C007
Example (default input configuration shown—see
page 3–84
):
See I/O specs on
page 4–6.
Required settings
A001
=
02
Notes:
•
This feature is available only when the frequency
command source is programmed for operator
control. Confirm
A001
is set to
02
.
•
This function is not available when [JG] is in use.
•
The range of output frequency is 0 Hz to the value
in
A004
(maximum frequency setting).
•
This setting modifies the inverter speed from using
F001
output frequency setting as a starting point.
DWN UP
7
6
5
4
3
2
1
L
PCS
P24
PLC
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...