Fine Tuning Functions
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Lnitial data Units
B001
Restart mode on power
failure / under-voltage trip
Select inverter restart method,
Five option codes:
00
…
Alarm output after trip, no
automatic restart
01
…
Restart at 0Hz
02
…
Resume operation after
frequency matching
03
…
Resume previous freq. after
freq. matching, then
decelerate to stop and display
trip info
04
…
Resume operation after active
freq. matching
U
00
−
B002
Allowable under-voltage
power failure time
The amount of time a power input
under-voltage can occur without
tripping the power failure alarm.
Range is 0.3 to 25 sec. If
under-voltage exists longer than
this time, the inverter trips, even
if the restart mode is selected.
U
1.0 sec.
B003
Retry wait time before motor
restart
Time delay after under-voltage
condition goes away, before the
inverter runs motor again.
Range is 0.3 to 100 seconds.
U
1.0 sec.
B004
Instantaneous power failure /
under-voltage trip alarm
enable
Three option codes:
00
…
Disable
01
…
Enable
02
…
Disable during stop and
decelerates to a stop
U
00
−
B005
Number of restarts on power
failure / under-voltage trip
events
Two option codes:
00
…
Restart 16 times
01
…
Always restart
U
00
−
b007
Restart frequency threshold
Restart the motor from 0Hz if the
frequency becomes less than this
set value during the motor is
coasting, range is 0 to 400Hz
U
0.00 Hz
b008
Restart mode on over voltage
/ over current trip
Select inverter restart method,
Five option codes:
00
…
Alarm output after trip, no
automatic restart
01
…
Restart at 0Hz
02
…
Resume operation after
frequency matching
03
…
Resume previous freq. after
active freq. matching, then
decelerate to stop and display
trip info
04
…
Resume operation after active
freq. matching
U
00
−
b010
Number of retry on over
voltage / over current trip
Range is 1 to 3 times
U
3
times
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...