Monitoring Parameters with the Display
After using the keypad for parameter editing, it’s a
good idea to switch the inverter from Program Mode
to Monitor Mode. The PRG LED will be OFF, and the
Hertz or Ampere LED indicates the display units.
For the powerup test, monitor the motor speed
indirectly by viewing the inverter’s output frequency.
The output frequency must not be confused with base
frequency (50/60 Hz) of the motor, or the carrier
frequency (switching frequency of the inverter, in the
kHz range). The monitoring functions are in the “D”
list, located near the top left of the “Keypad
Navigation Map”on page 2-26.
Output frequency (speed) set –
Resuming keypad operation from the previous table,
follow the steps below.
Action
Display
Func./Parameter
(Starting point)
H004
Motor poles parameter
Press the ESC key four times
F001
F001
is selected
Press the SET key.
b100
Set frequency displayed
Running the Motor
If you have programmed all the parameters up to this point, you’re ready to run the
motor! First, review this checklist:
1.
Verify the power LED is ON. If not, check the power connections.
2.
Verify the Run Key Enable LED is ON. If it is OFF, check the
A002
setting.
3.
Verify the PRG LED is OFF. If it is ON, review the instructions above.
4.
Make sure the motor is disconnected from any mechanical load.
5.
Now, press the RUN key on the keypad. The RUN LED will turn ON.
6.
Press the [
U
] key for a few seconds. The motor should start turning.
7.
Press the STOP key to stop the motor rotation.
1
2
RUN
ESC
STOP/
RESET
SET
8888
RUN
PWR
Hz
ALM
A
PRG
d
.
0
.
0
.
1
.
Summary of Contents for WJ200 Series Software
Page 19: ...xviii Revisions Revision History Table No Revision Comments Date of Issue Operation Manual No ...
Page 295: ...4 92 Safe Stop Function To be finalized after TUV approval ...
Page 296: ...5 1 5 Inverter System Accessories In This Chapter page Introduction 2 Component Description 3 ...
Page 322: ...A 1 A Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 ...
Page 378: ...B 49 Note 2 Be sure not to write into above 1F02h to 1F1Dh ...