11. Distribution fuse / circuit breaker size marking is included in the manual to indicate that the unit shall be
connected with a Listed inverse time circuit breaker, rated 600 V with the current ratings as shown in
the table below:
Model No.
Fuse Size (Maximum A)
Circuit Breaker (Maximum A)
Type
Rating
Type
Rating
L700-110L
J
60 A
Inverse time
60 A
L700-150L
J
100 A
Inverse time
100 A
L700-185L
J
100 A
Inverse time
100 A
L700-220L
J
100 A
Inverse time
100 A
L700-300L
J
125 A
Inverse time
125 A
L700-370L
J
175 A
Inverse time
175 A
L700-450L
J
225 A
Inverse time
225 A
L700-550L
J
250 A
Inverse time
250 A
L700-750L
J
300 A
Inverse time
300 A
L700-110H
J
30 A
Inverse time
30 A
L700-150H
J
40 A
Inverse time
40 A
L700-185H
J
50 A
Inverse time
50 A
L700-220H
J
50 A
Inverse time
50 A
L700-300H
J
75 A
Inverse time
75 A
L700-370H
J
80 A
Inverse time
80 A
L700-450H
J
100 A
Inverse time
100 A
L700-550H
J
125 A
Inverse time
125 A
L700-750H J 150A
Inverse
time
150
A
L700-900H
J
225 A
Inverse time
225 A
L700-1100H
J
225 A
Inverse time
225 A
L700-1320H
J
300 A
Inverse time
300 A
L700-1600H
J
350 A
Inverse time
350 A
12. “Field wiring connection must be made by a UL Listed and CSA Certified ring lug terminal connector
sized for the wire gauge being used. The connector must be fixed using the crimping tool specified by
the connector manufacturer.”
Summary of Contents for L700 Series
Page 16: ... Memo ...
Page 20: ... Memo ...
Page 22: ... Memo ...
Page 46: ... Memo ...
Page 60: ... Memo ...
Page 62: ... Memo ...
Page 212: ... Memo ...
Page 222: ... Memo ...
Page 224: ... Memo ...
Page 232: ... Memo ...
Page 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Page 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Page 240: ... Memo ...
Page 242: ... Memo ...
Page 258: ... Memo ...