Safety Instructions
v
Precautions Concerning Electromagnetic Compatibility (EMC)
The L700 series inverter conforms to the requirements of Electromagnetic Compatibility (EMC) Directive
(2004/108/EC). However, when using the inverter in Europe, you must comply with the following
specifications and requirements to meet the EMC Directive and other standards in Europe:
WARNING: This equipment must be installed, adjusted, and maintained by qualified engineers who
have expert knowledge of electric work, inverter operation, and the hazardous circumstances that can
occur. Otherwise, personal injury may result.
1. Power supply requirements
a. Voltage fluctuation must be -15% to +10% or less.
b. Voltage imbalance must be ±3% or less.
c. Frequency variation must be ±4% or less.
d. Total harmonic distortion (THD) of voltage must be ±10% or less.
2. Installation requirement
a. A special filter intended for the L700 series inverter must be installed.
3. Wiring requirements
a. A shielded wire (screened cable) must be used for motor wiring, and the length of the cable must be
according to the following table (Table 1).
b. The carrier frequency must be set according to the following table to meet an EMC requirement
(Table 1).
c. The main circuit wiring must be separated from the control circuit wiring.
4. Environmental requirements (to be met when a filter is used)
a. Ambient temperature must be within the range -10°C to +40°C.
b. Relative humidity must be within the range 20% to 90% (non-condensing).
c. Vibrations must be 5.9 m/s
2
(0.6 G) (10 to 55 Hz) or less. (11 to 30kW)
2.94 m/s
2
(0.3 G) (10 to 55Hz) or less. (37 to 160kW)
d. The inverter must be installed indoors (not exposed to corrosive gases and dust) at an altitude of
1,000 m or less.
model cat.
cable
length(m)
carrier
frequency(kHz)
model cat.
cable
length(m)
carrier
frequency(kHz)
L700-110L
C3 1
1 L700-110H
C3
1 2.5
L700-150L
C3 1
1 L700-150H
C3
1 2.5
L700-185L
C3 1
1 L700-185H
C3
1 2.5
L700-220L
C3 1
1 L700-220H
C3
1 2.5
L700-300L
C3 5
2.5 L700-300H
C3
1 2.5
L700-370L
C3 5
2.5 L700-370H
C3
1 2.5
L700-450L
C3 5
2.5 L700-450H
C3
1 2.5
L700-550L
C3 20
3 L700-550H
C3
5 2.5
L700-750L
C3 20
3 L700-750H
C3
5 2.5
L700-900H
C3
10 2.5
L700-110H
C3
10 2.5
L700-1320H
C3
10 2.5
L700-1600H
C3
10 2.5
Table 1
!
Summary of Contents for L700 Series
Page 16: ... Memo ...
Page 20: ... Memo ...
Page 22: ... Memo ...
Page 46: ... Memo ...
Page 60: ... Memo ...
Page 62: ... Memo ...
Page 212: ... Memo ...
Page 222: ... Memo ...
Page 224: ... Memo ...
Page 232: ... Memo ...
Page 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Page 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Page 240: ... Memo ...
Page 242: ... Memo ...
Page 258: ... Memo ...