Chapter 4 Explanation of Functions
4 - 44
4.2.35 Carrier frequency setting
The carrier frequency setting function (b083) allows you to change the
carrier frequency of the PWM waveform output from the inverter.
Increasing the carrier frequency can lower the metallic noise from the motor, but may increase the inverter
noise and current leakage.
You can use this function effectively to avoid resonance of the mechanical system and motor.
Item
Function code
Range of data
Description
Carrier frequency
setting
b083
0.5 to 12.0 (kHz) (*1)
<0.5 to 8.0(kHz)> (*2)
*1 The maximum carrier frequency varies depending on the inverter capacity.
When increasing the carrier frequency (fc), derate the output current as shown in the following table:
Derated output current is to be set as electronic thermal protection level (4.2.29).
Derating is not needed when electronic thermal level is already set to lower then derating level.
*2 < >:applied for 90 to 160kW
*3 “Over current protection” , ” Overload restriction” , “Over current limiting” and “Electronic thermal
protection” might operate from the set value when “Carrier frequency setting” is used with less than
2kHz by a low value. Please set to 2kHz or more and use the setting of “Carrier frequency setting” for
such a situation.
Voltage
class
200 V class
400 V class
Inverter
capacity
Maximum
fc (kHz)
Derating at fc=12 kHz
Maximum
fc (kHz)
Derating at fc=12 kHz
<Derating at fc=8kHz>
11kW 12
100%
12
100%
15kW 7 90%(52.2Aor
less) 12
100%
18.5kW 8 90%(65.7Aor
less) 12
100%
22kW 6 90%(76.5Aor
less) 8 95%(40.8Aor
less)
30kW 5 90%(101.7Aor
less) 8 90%(51.3Aor
less)
37kW
8
80%(112Aor less)
10
80%(56.0Aor less)
45kW 3 75%(126.7Aor
less) 9 90%(76.5Aor
less)
55kW 8 90%(189Aor
less) 8 80%(84Aor
less)
75kW 3 90%(243Aor
less) 6
75%(101.2Aor
less)
90kW -
-
7
90%(144Aor
less)
110kW -
-
3 80%(156Aor
less)
132kW -
-
4
85%(195.5Aor
less)
160kW -
-
3 70%(203Aor
less)
< > indicate the setting range of 90 to 160kW
Carrier frequency (kHz)
Derating of o
utpu
t current
60
55
100
95
90
85
80
75
70
65
15kW
18.5kW,55kW
200Vclass
0.5 2
4 6 8 10 12
30kW
37kW
22kW
45kW
75kW
Carrier frequency (kHz)
Derating of o
utpu
t current
60
55
100
95
90
85
80
75
70
65
45kW
22kW
400Vclass
0.5 2
4
6
8 10 12
55kW
11-18.5kW
30kW
37kW
75kW
90kW
110kW
132kW
160k
Summary of Contents for L700 Series
Page 16: ... Memo ...
Page 20: ... Memo ...
Page 22: ... Memo ...
Page 46: ... Memo ...
Page 60: ... Memo ...
Page 62: ... Memo ...
Page 212: ... Memo ...
Page 222: ... Memo ...
Page 224: ... Memo ...
Page 232: ... Memo ...
Page 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Page 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Page 240: ... Memo ...
Page 242: ... Memo ...
Page 258: ... Memo ...