Chapter 4 Explanation of Functions
4 - 69
4.2.66 Logical output signal operation function (LOG1 to LOG6)
The logical output signal operation function allows you to make
the inverter internally perform a logical operation of output
signals.
This function applies to all output signals, except to logical
operation results (LOG1 to LOG6).
Three types of operators (AND, OR, and XOR) are selectable.
The necessary parameters depend on the logical output signal to be operated. The following table lists the
parameters to be set for each logical output signal:
Selected signal
Operation-target 1
selection
Operation-target 2
selection
Operator
selection
33: Logical output signal 1 (LOG1)
C142
C143
C144
34: Logical output signal 2 (LOG2)
C145
C146
C147
35: Logical output signal 3 (LOG3)
C148
C149
C150
36: Logical output signal 4 (LOG4)
C151
C152
C153
37: Logical output signal 5 (LOG5)
C154
C155
C156
38: Logical output signal 6 (LOG6)
C157
C158
C159
(Example) To output the AND of the running signal (00: RUN) and set the frequency overreached signal
(02: FA2) as the logical output signal 1 (LOG1) to the intelligent output terminal [2]:
- Intelligent output terminal [2] (C002): 33 (LOG1)
- Logical output signal 1 selection 1 (C142): 00 (RUN)
- Logical output signal 1 selection 2 (C143): 02 (FA2)
- Logical output signal 1 operator (C143): 00 (AND)
Item
Function code
Data or range of data
Description
Terminal function
C021 to C025
C026
33
LOG1: Logical operation result 1
(C142, C143, and C144)
34
LOG2: Logical operation result 2
(C145, C146, and C147)
35
LOG3: Logical operation result 3
(C148, C149, and C150)
Alarm relay
terminal function
36
LOG4: Logical operation result 4
(C151, C152, and C153)
37
LOG5: Logical operation result 5
(C154, C155, and C156)
38
LOG6: Logical operation result 6
(C157, C158, and C159)
Logical output
signal selection 1
C142/C145/C148/
C151/C154/C157
Selection of "00" to "56" from the
data (except LOG1 to LOG6) output
to intelligent output terminals
Selection of operation-target 1
Logical output
signal selection 2
C143/C146/C149/
C152/C155/C158
Selection of "00" to "56" from the
data (except LOG1 to LOG6) output
to intelligent output terminals
Selection of operation-target 2
Logical output
signal operator
selection
C144/C147/C150/
C153/C156/C159
00
AND
01
OR
02
XOR
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C142: Logical output signal 1 selection 1
C143: Logical output signal 1 selection 2
C144: Logical output signal 1 operator selection
C145: Logical output signal 2 selection 1
C146: Logical output signal 2 selection 2
C147: Logical output signal 2 operator selection
C148: Logical output signal 3 selection 1
C149: Logical output signal 3 selection 2
C150: Logical output signal 3 operator selection
C151: Logical output signal 4 selection 1
C152: Logical output signal 4 selection 2
C153: Logical output signal 4 operator selection
C154: Logical output signal 5 selection 1
C155: Logical output signal 5 selection 2
C156: Logical output signal 5 operator selection
C157: Logical output signal 6 selection 1
C158: Logical output signal 6 selection 2
C159: Logical output signal 6 operator selection
Related code
LOGx (AND)
LOGx (OR)
LOGx (XOR)
Output signal 1
Output signal 2
Summary of Contents for L700 Series
Page 16: ... Memo ...
Page 20: ... Memo ...
Page 22: ... Memo ...
Page 46: ... Memo ...
Page 60: ... Memo ...
Page 62: ... Memo ...
Page 212: ... Memo ...
Page 222: ... Memo ...
Page 224: ... Memo ...
Page 232: ... Memo ...
Page 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Page 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Page 240: ... Memo ...
Page 242: ... Memo ...
Page 258: ... Memo ...