Chapter 4 Explanation of Functions
4 - 109
(viii) 07 command: This command writes data to a specified setting item in the inverter.
- Transmission frame
Frame format
STX Station
No.
Command
Parameter
Data BCC CR
Description
Data
size Setting
STX
Control code (Start of TeXt)
1 byte
STX (0x02)
Station No.
Station number of control-target
inverter
2 bytes
01 to 32, or FF (broadcast to all stations)
Command Command to be transmitted
2 bytes
07
Parameter Data parameter number
4 bytes
See Note 14.
Data
Parameter data (decimal ASCII
code)
8 bytes
See Note 13.
BCC
Block check code
2 bytes
XOR of the items from "Station No." to "Data."
See Item (3) of this section.
CR
Control code (Carriage Return)
1 byte
CR (0x0D)
Note 14: Possible range of parameters is as follows.
F002-, A001-, b001-, C001-, H001-, P001- (F001 is written with 01 command.)
- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.
(ix) 08 command: This command initializes specified settings in the inverter.
The setting items to be initialized follow the setting of the initialization mode (b084). When "b084" is "00",
the trip history data is cleared.
- Transmission frame
Frame format
STX Station
No.
Command BCC
CR
Description
Data
size Setting
STX
Control code (Start of TeXt)
1 byte
STX (0x02)
Station No.
Station number of control-target
inverter
2 bytes
01 to 32, or FF (broadcast to all stations)
Command Command to be transmitted
2 bytes
08
BCC
Block check code
2 bytes
XOR of the items from "Station No." to "Data."
See Item (3) of this section.
CR
Control code (Carriage Return)
1 byte
CR (0x0D)
- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.
Summary of Contents for L700 Series
Page 16: ... Memo ...
Page 20: ... Memo ...
Page 22: ... Memo ...
Page 46: ... Memo ...
Page 60: ... Memo ...
Page 62: ... Memo ...
Page 212: ... Memo ...
Page 222: ... Memo ...
Page 224: ... Memo ...
Page 232: ... Memo ...
Page 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Page 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Page 240: ... Memo ...
Page 242: ... Memo ...
Page 258: ... Memo ...