Chapter 2 Installation and Wiring
2 - 22
2.2.5 Selection and wiring of regenerative braking resistor (on 11 kW to 30 kW models)
The L700 series inverter models with capacities of 11 to 30 kW have an internal regenerative braking
circuit.
Connecting an optional regenerative braking resistor to RB and P terminals increases the regenerative
torque.
Model
Motor capacity
(kW)
Without a resistor
connected
Minimum connectable resistor
Minimum
resistance
during
continuous
operation
(
Ω
)
Regenerative
torque (%)
Resistance
(
Ω
)
Regenerativ
e torque
(
%
)
BRD usage
rate
(
%
)
L700-110LFF 11
10
10 110 10
50
L700-150LFF 15
10
10 80 10
50
L700-185LFF 18.5
10
7.5 90
10
35
L700-220LFF 22
10
7.5 70 10
35
L700-300LFF 30
10
5 80 10
35
L700-110HFF 11
10
35
120
over 10 150
L700-150HFF 15
10
35 90 10 100
L700-185HFF 18.5
10
24 110 10
100
L700-220HFF 22
10
24 90 10 100
L700-300HFF 30
10
20 80 10 100