Chapter 4 Explanation of Functions
4 - 135
Register
No.
Function name
Function
code
R/W
Monitoring and setting items Data resolution
Register
No.
1326h
Reduced voltage start selection
b036
R/W 0 (minimum reduced voltage start time) to 255
(maximum reduced voltage start time)
-
1327h
Function code display restriction
b037
R/W 0 (full display), 1 (function-specific display), 2 (user
setting), 3 (data comparison display), 4 (basicdisplay)
-
1328h Initial-screen
selection
b038
R/W 0 (screen displayed when the STR key was pressed
last), 1 (d001), 2 (d002), 3 (d003), 4 (d007), 5 (F001)
-
1329h
Automatic user-parameter
setting function enable
b039
R/W 0 (disabling), 1 (enabling)
-
132Ah Torque limit selection
b040
R/W
00 (quadrant-specific setting), 01 (switching by
terminal), 02 (analog input), 03 (option 1),
04 (option 2)
-
132Bh Torque limit (1) (forward-driving
in 4-quadrant mode)
b041
R/W 0 to 150 (no)
1 [%]
132Ch
Torque limit (2)
(reverse-regenerating in
4-quadrant mode)
b042
R/W 0 to 150 (no)
1 [%]
132Dh Torque limit (3) (reverse-driving
in 4-quadrant mode)
b043
R/W 0 to 150 (no)
1 [%]
132Eh
Torque limit (4)
(forward-regenerating in
4-quadrant mode)
b044
R/W 0 to 150 (no)
1 [%]
132Fh
Torque limit LADSTOP enable
b045
R/W 0 (disabling), 1 (enabling)
-
1330h
Reverse Run protection enable
b046
R/W 0 (disabling), 1 (enabling)
-
1331h to
1333h
(Reserved) -
-
Inaccessible
-
1334h
Controller deceleration and stop
on power loss
b050 R/W
0 (disabling), 1 (enabling), 2, (nonstop operation at
momentary power failure (no restoration))
3, (nonstop operation at momentary power failure
(restoration to be done))
-
1335h
DC bus voltage trigger level
during power loss
b051
R/W 0 to 10000
0.1 [V]
1336h
Over-voltage threshold during
power loss
b052
R/W 0 to 10000
0.1 [V]
1337h
Deceleration time setting during
power loss (target voltage level)
b053 (high)
R/W
0 to 360000
0.01
[sec.]
1338h b053
(low)
R/W
1339h
Initial output frequency decrease
during power loss
b054
R/W 0 to 1000
0.01 [Hz]
133Ah
Proportional gain setting for
nonstop operation at momentary
power failure
b055
R/W 0 to 255
0.01
133Bh
Integral time setting for nonstop
operation at momentary power
failure
b056
R/W 0 to 65535
0.001
[sec]
133Ch to
133Eh (Reserved) -
-
Inaccessible
-
133Fh
Maximum-limit level of window
comparators O
b060 R/W
0. to 100. (lower limit : b061 + b062 *2) (%)
1 [%]
1340h
Minimum-limit level of window
comparators O
b061 R/W
0. to 100. (lower limit : b060 - b062*2) (%)
1 [%]
1341h
Hysteresis width of window
comparators O
b062 R/W
0. to 10. (lower limit : b061 - b062 / 2) (%)
1 [%]
1342h
Maximum-limit level of window
comparators OI
b063 R/W
0. to 100. (lower limit : b064 + b066 *2) (%)
1 [%]
1343h
Minimum-limit level of window
comparators OI
b064 R/W
0. to 100. (lower limit : b063 - b066 *2) (%)
1 [%]
1344h
Hysteresis width of window
comparators OI
b065 R/W
0. to 10. (lower limit : b063 - b064 / 2) (%)
1 [%]
1345h
Maximum-limit level of window
comparators OI
b066 R/W
-100. to 100. (lower limit : b067 + b068 *2) (%)
1 [%]
1346h
Minimum-limit level of window
comparators O/OI/O2
b067 R/W
-100. to 100. (lower limit : b066 - b068 * 2) (%)
1 [%]
1347h
Hysteresis width of window
comparators O/OI/O2
b068 R/W
0. to 10. (lower limit : b066 - b067 / 2) (%)
1 [%]
1348h (Reserved)
-
-
Inaccessible
-
1349h
Operation level at O
disconnection
b070 R/W
0. to 100. (%) or "no" (ignore)
1 [%]
134Ah Operation level at OI
disconnection
b071 R/W
0. to 100. (%) or "no" (ignore)
1 [%]
134Bh Operation level at O2
disconnection
b072 R/W
-100. to 100. (%) or "no" (ignore)
1 [%]
134Ch to
1350
(reserved) -
-
Inaccessible
-
1351h
Cumulative input power data
clearance
b060
R/W Clearance by setting "1"
-
1352h
Cumulative input power display
gain setting
b060
R/W 1 to 1000
1
Summary of Contents for L700 Series
Page 16: ... Memo ...
Page 20: ... Memo ...
Page 22: ... Memo ...
Page 46: ... Memo ...
Page 60: ... Memo ...
Page 62: ... Memo ...
Page 212: ... Memo ...
Page 222: ... Memo ...
Page 224: ... Memo ...
Page 232: ... Memo ...
Page 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Page 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Page 240: ... Memo ...
Page 242: ... Memo ...
Page 258: ... Memo ...