Chapter 4 Explanation of Functions
4 - 20
4.2.19 DC braking (DB) setting
The DC braking function allows you to apply DC braking to the
motor according to the load on the motor.
You can control DC braking in two ways: the external control
through signal input to intelligent input terminals and the internal
control to be performed automatically when the motor is started
and stopped.
Note that the motor cannot be stopped by DC braking if the load
on the motor produces a large moment of inertia.
Item
Function code
Data or range of data
Description
DC braking enable
A051
00
Internal DC braking is disabled.
01
Internal DC braking is enabled.
02
Internal DC braking is enabled. (The braking
operates only with the set braking frequency.)
DC braking
frequency setting
A052
0.00 to 60.00 (Hz)
With internal DC braking enabled, DC braking is
started when the output frequency reaches the
set braking frequency.
DC braking wait
time
A053
0.0 to 5.0 (s)
The DC braking wait time specifies the delay in
starting DC braking after the set braking time has
elapsed or the DB terminal has been turned on.
DC braking force
during deceleration/
DC braking force for
starting
A054/A057
0. to 70. (%)
<0. to 50 (%)>
"0" specifies the smallest force (zero current);
"100" specifies the largest force (rated current).
DC braking time for
deceleration
A055
0.0 to 60.0 (s)
This setting is valid for the external DC braking in
edge mode or for the internal DC braking.
DC braking/edge or
level detection for
[DB] input
A056
00
Edge mode (See examples 1-a to 6-a.)
01
Level mode (See examples 1-b to 6-b.)
DC braking time for
starting
A058
0.0 to 60.0 (s)
This setting is valid for the internal DC braking.
DC braking is started when the motor-start
command is input.
DC braking carrier
frequency setting
A059
0.5 to 12(kHz)
<0.5 to 8 (kHz)>
Unit: kHz
(NOTE) <>:applied for 90 to 160kW
(1) Carrier frequency for DC braking
Use the DC braking carrier frequency setting (A059) to specify the carrier frequency for DC braking.
But the raking power reduced is reduced when 3kHz (up to 75kW) or 5kHz (90-160kW) are set as
shown below. For detailed decreasing ratio, "DC braking limiter" is to be referred.
DC braking force limiter(11-75kW)
DC braking force limiter(90-160kW)
A051: DC braking enable
A052: DC braking frequency setting
A053: DC braking wait time
A054: DC braking force during deceleration
A055: DC braking time for deceleration
A056: DC braking/edge or level detection for
[DB] input
A057: DC braking force for starting
A058: DC braking time for starting
A059: DC braking carrier frequency setting
C001 to C008: Terminal [1] to [8] functions
Related code
Maximum
braking
force (%)
DC braking carrier frequency(kHz)
0
70
60
50
40
30
20
10
3 12
11
9
5 7
(58)
(46)
(34)
(22)
(10)
Maximum
braking
force (%)
DC braking carrier frequency(kHz)
0
70
60
50
40
30
20
10
8
7
6
(50)
(25)
(10)
5
4
3
Summary of Contents for L700 Series
Page 16: ... Memo ...
Page 20: ... Memo ...
Page 22: ... Memo ...
Page 46: ... Memo ...
Page 60: ... Memo ...
Page 62: ... Memo ...
Page 212: ... Memo ...
Page 222: ... Memo ...
Page 224: ... Memo ...
Page 232: ... Memo ...
Page 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Page 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Page 240: ... Memo ...
Page 242: ... Memo ...
Page 258: ... Memo ...