Chapter 4 Explanation of Functions
4 - 143
Register
No.
Function name
Function code
R/W
Monitoring and setting items Data
resolution
Register
No.
1633h
Motor poles setting for RPM
P049
R/W
0 (0 pole), 1 (2 poles), 2 (4 poles), 3 (6
poles), 4 (8 poles), 5 (10 poles), 6 (12
poles), 7 (14 poles), 8 (16 poles), 9 (18
poles), 10 (20 poles), 11 (22 poles), 12
(24 poles), 13 (26 poles), 14 (28 poles),
15 (30 poles), 16 (32 poles), 17 (34
poles), 18 (36 poles), 19 (38 poles)
-
1634h to
1638h
(Reserved) -
-
Inaccessible
-
1639h
Pulse train frequency scale
P055
R/W
10 to 500 (input frequency corresponding
to the allowable maximum frequency)
0.1 [kHz]
163Ah
Time constant of pulse train frequency
filter
P056
R/W 1 to 200
0.01 [sec.]
163Bh Pulse train frequency bias
P057
R/W -100 to +100
1 [%]
163Ch Pulse train frequency limit
P058
R/W 0 to 100
1 [%]
163Dh (Reserved)
-
- Inaccessible
-
1656h to
1665h
(Reserved) -
-
Inaccessible
-
1666h
Easy sequence user parameter U (00)
P100
R/W 0 to 65530
1
1667h
Easy sequence user parameter U (01)
P101
R/W 0 to65530
1
1668h
Easy sequence user parameter U (02)
P102
R/W 0 to 65530
1
1669h
Easy sequence user parameter U (03)
P103
R/W 0 to 65530
1
166Ah Easy sequence user parameter U (04)
P104
R/W 0 to 65530
1
166Bh Easy sequence user parameter U (05)
P105
R/W 0 to 65530
1
166Ch Easy sequence user parameter U (06)
P106
R/W 0 to 65530
1
166Dh Easy sequence user parameter U (07)
P107
R/W 0 to 65530
1
166Eh Easy sequence user parameter U (08)
P108
R/W 0 to 65530
1
166Fh
Easy sequence user parameter U (09)
P109
R/W 0 to 65530
1
1670h
Easy sequence user parameter U (10)
P110
R/W 0 to 65530
1
1671h
Easy sequence user parameter U (11)
P111
R/W 0 to 65530
1
1672h
Easy sequence user parameter U (12)
P112
R/W 0 to 65530
1
1673h
Easy sequence user parameter U (13)
P113
R/W 0 to 65530
1
1674h
Easy sequence user parameter U (14)
P114
R/W 0 to 65530
1
1675h
Easy sequence user parameter U (15)
P115
R/W 0 to 65530
1
1676h
Easy sequence user parameter U (16)
P116
R/W 0 to 65530
1
1677h
Easy sequence user parameter U (17)
P117
R/W 0 to 65530
1
1678h
Easy sequence user parameter U (18)
P118
R/W 0 to 65530
1
1679h
Easy sequence user parameter U (19)
P119
R/W 0 to 65530
1
167Ah Easy sequence user parameter U (20)
P120
R/W 0 to 65530
1
167Bh Easy sequence user parameter U (21)
P121
R/W 0 to 65530
1
167Ch Easy sequence user parameter U (22)
P122
R/W 0 to 65530
1
167Dh Easy sequence user parameter U (23)
P123
R/W 0 to 65530
1
167Eh Easy sequence user parameter U (24)
P124
R/W 0 to 65530
1
167Fh
Easy sequence user parameter U (25)
P125
R/W 0 to 65530
1
1681h
Easy sequence user parameter U (27)
P127
R/W 0 to 65530
1
1682h
Easy sequence user parameter U (28)
P128
R/W 0 to 65530
1
1683h
Easy sequence user parameter U (29)
P129
R/W 0 to 65530
1
1684h
Easy sequence user parameter U (30)
P130
R/W 0 to 65530
1
1685h
Easy sequence user parameter U (31)
P131
R/W 0 to 65530
1
1686h to
2102h
(Reserved) -
-
Inaccessible
-
*1 The following table lists the code data for parameter "H003" (motor capacity selection):
Code
data
00 01 02 03 04 05 06 07 08 09 10
Motor
capacity
0.2
kW
- 0.4
- 0.75
- 1.5
2.2 - 3.7
-
Code
data
11 12 13 14 15 16 17 18 19 20 21
Motor
capacity
5.5
kW
7.5
11 15 18.5
22 30 37 45 55 75
Code
data
22
23
24
25
26
Motor
capacity
90kW
110
132
150
160
Summary of Contents for L700 Series
Page 16: ... Memo ...
Page 20: ... Memo ...
Page 22: ... Memo ...
Page 46: ... Memo ...
Page 60: ... Memo ...
Page 62: ... Memo ...
Page 212: ... Memo ...
Page 222: ... Memo ...
Page 224: ... Memo ...
Page 232: ... Memo ...
Page 238: ...Chapter 7 Specifications 7 6 L700 750 LFF 6 Cable hole φ41 ...
Page 239: ...Chapter 7 Specifications 7 7 L700 900 to 1100HFF L700 1320 to 1600HFF ...
Page 240: ... Memo ...
Page 242: ... Memo ...
Page 258: ... Memo ...