Chapter 6 List of Parameters GK600E User Manual
- 94 -
Parameter
Designation
Scope
Factory
default
Attr
0.7kHz~10.0kHz, factory default:
4.0 kHz
55kW~75kW:
0.7kHz~16.0kHz, factory default:
3.0 kHz
≥90kW:
0.7kHz~3.0kHz, factory default:
2.0 kHz
E0-01
PWM optimization
Ones place: sw itching FREQ relation
w ith temperature
0: Self-adaption
1: No adaption
Tens place: PWM modulation mode
0: Five-segment and seven-segment
self-sw itchover
1: Five-segment mode
2: Seven-segment mode
Hundreds place: over-modulation
adaption
0: Disabled
1: Enabled
Thousands place: PWM sw itching
FREQ relation w ith output frequency
0: Self-adaption
1: No adaption
1001
×
E0-02
Action w hen run time
attained
Ones place: action w hen consecutive
run time attained:
0: Run continued
1: Stop and fault reported
Tens place: action w hen
accumulative run time attained:
0: Run continued
1: Stop and fault reported
Hundreds place: unit of run time
0: Second
1: Hour
000
×
E0-03
Consecutive run time
setting
0.0s(h)~6000.0s(h)
0.0 s(h)
×
E0-04
Accumulative run time
setting
0.0s(h)~6000.0s(h)
0.0 s(h)
×
E0-05
V/F current proportional
0~60000
50
×