Chapter 6 List of Parameters GK600E User Manual
- 80 -
Parameter
Designation
Scope
Factory
default
Attr
b1-01
Binding of run command
and frequency set
Ones place: frequency set bundled
under control panel control:
0: No binding
1: Digital setting (b0-02) +
∧
/
∨
adjustment on control panel
2: Digital setting (b0-02) + terminal
UP/DOWN adjustment
3: Analog input AI1
4: Analog input AI2
5: Analog input EAI (on IO option
board)
6: X6/DI pulse input
7: Process PID output
8: Simple PLC
9: Multi-step FREQ
A: Communication input
Tens place: FREQ set bundled under
terminal control (same as ones place)
Hundreds place: FREQ set bundled
under communication control (same
as ones place)
090
×
b1-02
Run direction
0: Forw ard
1: Reverse
0
△
b1-03
Reverse disabled
0: Reverse enabled
1: Reverse disabled
0
×
b1-04
Dead time betw een forward
and reverse
0.0s~3600.0s
0.0s
△
b1-05
Start method
0: From start FREQ
1: DC braking start
2: Flying start 1
3: Flying start 2
1
×
b1-06
Start FREQ
0.00Hz~upper limit FREQ
0.00Hz
×
b1-07
Holding time of start FREQ 0.0s~3600.0s
0.0s
△
b1-08
DC braking current at start 0.0%
~
200.0%
80.0%
△
b1-09
DC braking time at start
0.00s~30.00s
0.50s
△
b1-10
Flying start 1 current
0.0~200.0%
100.0%
×
b1-11
Flying start 1 Decel time 0.1s~20.0s
2.0s
×
b1-12
Flying start 1 adjustment
coeff
20.0%
~
100.0%
100.0%
×
b1-13
Stop method
0: Ramp to stop
1: Coast to stop
2
×