GK600E User Manual
Chapter 3 Installation and Wiring
- 25 -
other terminals since this w ill result in short circuit and equipment damage.
Wiring screw s and bolts for main circuit terminals must be screw ed tightly. Failure to
comply may result in faults and/or equipment damage.
ATTENTION
Signal w ires should be aw ay from main pow er lines to the best of possibility. In the
event that this cannot be ensured, vertical cross arrangement should be adopted,
reducing EMI interference to the signal w ires as much as possible.
In case the motor cable exceeds 100m, an appropriate output reactor should be
mounted.
3.6.1 Main Circuit Terminals of GK600E-4T3.7B ~ GK600E-4T30B
Terminal marks
Designation and function of terminals
R/L1, S/L2, T/L3
Three-phase AC input terminals
,
DC reactor connection terminals. Connected w ith a
jumper as factory default
, B2
Built-in brake unit connection terminals*
,
DC input terminals of externally mounted brake unit
,
DC pow er supply input terminals
U/T1, V/T2, W/T3
Three-phase AC output terminals
Ground terminal PE
-
+ 1
+ 2/B1
+ 2/B1
+ 2/B1
-
+ 1