GK600E User Manual
Chapter 4 Operation and Run Instructions
- 41 -
Stop/reset key
1) Stop
2) Fault reset
Multi-function
key
See Table 4-2 " MF key function definition"
Table 4-2 MF key function definition
L0-00 set
value
Function of MF key
Meaning
0
Disabled
MF key disabled
1
Forw ard JOG
Forw ard JOG function
2
Reverse JOG
Reverse JOG function
3
Forw ard/Reverse
sw itch
Run direction forw ard and reverse sw itching
4
Emergency
STOP 1
Press
to STOP, w ith ramp-dow n time b2-09
5
Emergency
STOP 2
Coast to stop, the drive cuts off output
6
Run command
setting mode
sw itch
Control
panel
control
->
Terminal
control
->
Communication control -> Control panel control, press
to confirm w ithin 5 seconds
4.1.2 Control Panel Indicators
Control panel is furnished w ith 7 indicators w hose descriptions are as below
Table 4-3 Description of indicators
Indicator
Designation
Meaning
Hz
Frequency indicator
ON: currently displayed parameter value is run
frequency or the current parameter unit is
frequency
Flash: currently displayed parameter value is set
frequency
A
Current indicator
ON: currently displayed parameter value is current
V
Voltage indicator
ON: currently displayed parameter value is voltage
Hz+A
Run speed indicator
ON: currently displayed parameter value is run
speed
Flash: currently displayed parameter value is
setting speed
A+V
Percentage indicator
ON: currently displayed parameter value is a
percentage value
All OFF
No unit
No unit
MON
Run command setting
mode indicator
ON: Control panel
OFF: Terminal
Flash: Communication
RUN
Run status indicator
ON: Run