Chapter 3 Installation and Wiring GK600E User Manual
- 30 -
3.8 Control Terminal Specification
Table 3-5 Control terminal specification
Category
Terminal
Terminal
designation
Specification
Analog
input
+10V
Analog input
reference
voltage
10.3V ±3%
Maximum output current 25mA
The resistance of external potentiometer
should be larger than 400
Ω
GND
Analog ground
Isolated from COM interiorly
AI1
Analog input 1
0~20mA: input impedance - 500
Ω, maximum
input current - 25mA
0~10V: input impedance - 22k
Ω,
maximum input voltage - 12.5V
Sw itch S2 on control board for jumping from
0~20mA and 0~10V, factory default: 0~10V
AI2
Analog input 2
-10V~10V: input impedance - 25k
Ω
Range: -12.5V~+12.5V
Analog
output
AO1
Analog output 1
0~20mA: impedance -
200Ω~500Ω
0~10V: impedance ≥ 10k
Sw itch S3 on control board for jumping from
0~20mA to 0~10V, factory default: 0~10V
GND
Analog ground
Isolated from COM interiorly
Digital
input
+24V
+24V
24V±10%, Isolated from GND interiorly
Maximum load - 200mA
PLC
Digital input
Common
terminal
Used for sw itching betw een high and low
levels, short-circuited w ith +24V w hen
delivery, i.e. low value of digital input valid
External pow er input
COM
+24V ground
Isolated from GND interiorly
X1~X6
Digital input
Terminals 1~5
Input: 24VDC, 5mA
Range of frequency: 0~200Hz
Range of voltage: 10V~30V
X7
Digital input (on
option board)
Digital input: same as X1~X5
Digital
output
Y1
Open collector
output
Range of voltage: 0~24V
Range of current: 0~50mA
Y2/DO
Open collector
out / Pulse out
Open collector output: same as Y1
Pulse output: 0~50kHz;