Chapter 3 Installation and Wiring GK600E User Manual
- 26 -
3.6.2 Terminal Screw and Wiring Requirement
Table 3-4 Terminal screw and wiring requirement
■GK600E-4T
B Three-phase 400V input
Drive model
Pow er terminal
Ground terminal
Cable
requirement
(mm
2
)
Screw
Torque
(kgf.cm)
Cable
requirement
(mm
2
)
Screw
Torque
(kgf.cm)
GK600E-4T3.7B
2.5
M4
14±0.5
2.5
M4
14±0.5
GK600E-4T5.5B
4
M4
14±0.5
4
M4
14±0.5
GK600E-4T7.5B
4
M4
14±0.5
4
M4
14±0.5
GK600E-4T11B
6
M5
28±0.5
6
M4
14±0.5
GK600E-4T15B
10
M5
28±0.5
10
M4
14±0.5
GK600E-4T18.5B
10
M6
48±0.5
10
M6
48±0.5
GK600E-4T22B
16
M6
48±0.5
16
M6
48±0.5
GK600E-4T30B
25
M6
48±0.5
16
M6
48±0.5
3.7 Control Terminal Wiring
WARNING
Only qualified personnel familiar w ith AC motor drives and passenger lift are allow ed to
implement w iring. Failure to comply may result in equipment damage and/or personnel
injury even death.
Wiring should be in strict accordance w ith this manual, otherw ise hazard of electric
shock or equipment damage exists.
Make sure input pow er supply has been completely disconnected before w iring
operation. Failure to comply w ill result in personnel injury even death.
All w iring operations and lines should comply w ith EMC and national and local industrial
safety regulations and/or electrical codes. The conductor diameter should be in
accordance w ith recommendations of this manual. Otherw ise, hazard of equipment